150-F480NCD Allen Bradley

Cross references: 150-F480NCR150-F480NBD150-F480NBR150-F480NZD150-F480NBDB150-F480NCDB Amperage: 480 Amps Voltage: 200 HP at 230 V 400 HP at 460 V 500 HP at 600 V Serial: SMC Flex FREE INSPECTION FOR SOFTSTARTS UNDER 100 HP.

Numéro de pièce du fabricant : 

123-456-789

Manufacturer part number : 

150-F480NCD

Détails

150-F480NCD Allen Bradley


Serial SMC Flex

 

The SMC Flexand its modular design is an ideal fit for the existing system.

Minimizes starting peak current and torque shock to the system. Smart Motor Braking option stops the motor in 2 minutes versus the coast-down time of 15 minutes. Slow Speed operation enables inspection of saw blade tracking before the motor is brought to full speed. Current, Voltage, and Power diagnostics displayed via a door-mounted HIM interface. Built-in programmable overload protection accommodates characteristics of a high-inertia load. Diagnostics detect jam, stall, or single phasing and shut off the motor, helping to prevent damage.

 


Error codes

 

 

 

 

Fault name : Shorted SCR with phase indication (Code 4,5 or 6)

Possible causes : Shorted power module

Possible solutions : Check for shorted SCR, replace power module if necessary

 

Fault name : Open gate with phase indication (Code 7,8 or 9)

Possible causes : Open gate circuitry

                          Loose gate lead

Possible solutions : Perform resistance check; replace power module if necessary

                            Check gate lead connections to the control module

 

Fault name : PTC power pole and SCR Overtemp (Code 10 or 11)

Possible causes : Controller ventilation blocked

                         Controller duty cycle exceeded

                         Fan failure

                         Ambient temperature limit exceeded

                         Failed thermistor

Possible solutions : Check for proper ventilation

                             Check application duty cycle

                             Wait for motor to cool or provide external cooling

                             Replace power module or control module as needed

                             Replace fan

 

Fault name : Motor PTC (Code 12)

Possible causes : Motor ventilation blocked

                          Motor duty cycle exceeded

                          PTC open or shorted

Possible solutions : Check for proper ventilation

                             Check application duty cycle

                             Wait for motor to cool or provide external cooling

                             Check resistance of PTC

 

Fault name : Open Bypass with phase indication (Code 13, 14 or 15)

Possible causes : Control voltage is low

                         Inoperable power module bypass

Possible solutions : Check control voltage power supply

                             Replace power module

                             Check control module TB2…TB4 and TB5…TB7 for securness

                             Check Aux 1, 2, 3, 4 configurations are not sent to External Bypass

 

Fault name : No load fault (Code 16, 17, 18 or 40)

Possible causes : Loss or load side power wiring

                         Start command cycled unexpectedly with motor rotating

Possible solutions : Check all load side power connections

                            Check motor windings

 

Fault name : Line unbalance (Code 19)

Possible causes : Supply unbalance is greater than the user-programmed value

                         The delay time is too short for the application

Possible solutions : Check power system and correct if necessary

                             Extend the delay time to match the application requirements

 

 

Fault name : Overvoltage (Code 20)

Possible causes : Supply voltage is greater than user programmed value

                         The delay time is too short for the application

Possible solutions : Check power system and correct if necessary

                            Correct the user-programmed value

                             Extend the delay time to match the application requirements.

 

Fault name : Undervoltage (Code 21)

Possible causes : Supply voltage is less than user programmed value

                         The delay time is too short for the application

Possible solutions : Check power system and correct if necessary

                             Correct the user-programmed value

                             Extend the delay time to match the application requirements.

 

Fault name : Overload (Code 22)

Possible causes : Motor overloaded

                          Overload parameters are not matched to the motor

Possible solutions : Check motor overload condition

                             Check values for overload class and motor FLC

                             Verify current draw of the motor

 

Fault name : Undervoltage (Code 23)

Possible causes : Broken motor shaft, belts, toolbits etc…

                         Pump cavitation

                         Incorrect user setting

Possible solutions : Check pump system, machine drive components, and loading

                            Check settings

                             Repair or replace motor

 

Fault name : Jam (Code 24)

Possible causes : Motor current has exceeded the user programmed jam level

Possible solutions : Correct source of jam or excessive loading

                             Check programmed time value

 

 

 

Fault name : Ground fault (Code 33)

Possible causes : Ground fault current level has exceeded programmed value

                          The delay time is too short for the application

Possible solutions : Check power system and motor; correct if necessary

                             Check programmed ground fault levels to match application requirements

                             Extend the delay time to match the application requirements

 

Fault name : Power loss with phase indication (Code 35, 36 or 37)

Possible causes : Missing supply phase (as indicated)

                         Internal CR problem

Possible solutions : Check for open line (i.e., blown line fuse)

                            Replace power pole as indicated

 

Fault name : Line loss with phase indication (Code 41, 42 or 43)

Possible causes : Incoming 3-phrase voltage instability or distortion

                         High impedance connection

Possible solutions : Check supply voltage for capability to start/stop motor

                             Check for loose connections on line side or motor side or power wires

                             Verify and correct input power quality

Équivalents:
150-F480NCR
150-F480NBD
150-F480NBR
150-F480NZD
150-F480NBDB
150-F480NCDB
Ampérage: 480 Ampères
Tension:
200 HP à 230 V
400 HP à 460 V
500 HP à 600 V
Série: SMC Flex