150-F480NCD Allen Bradley
Numéro de pièce du fabricant :
123-456-789
Manufacturer part number :
150-F480NCD
150-F480NCD Allen Bradley
Serial SMC Flex
The SMC Flexand its modular design is an ideal fit for the existing system.
Minimizes starting peak current and torque shock to the system. Smart Motor Braking option stops the motor in 2 minutes versus the coast-down time of 15 minutes. Slow Speed operation enables inspection of saw blade tracking before the motor is brought to full speed. Current, Voltage, and Power diagnostics displayed via a door-mounted HIM interface. Built-in programmable overload protection accommodates characteristics of a high-inertia load. Diagnostics detect jam, stall, or single phasing and shut off the motor, helping to prevent damage.
Error codes
Fault name : Shorted SCR with phase indication (Code 4,5 or 6)
Possible causes : Shorted power module
Possible solutions : Check for shorted SCR, replace power module if necessary
Fault name : Open gate with phase indication (Code 7,8 or 9)
Possible causes : Open gate circuitry
Loose gate lead
Possible solutions : Perform resistance check; replace power module if necessary
Check gate lead connections to the control module
Fault name : PTC power pole and SCR Overtemp (Code 10 or 11)
Possible causes : Controller ventilation blocked
Controller duty cycle exceeded
Fan failure
Ambient temperature limit exceeded
Failed thermistor
Possible solutions : Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling
Replace power module or control module as needed
Replace fan
Fault name : Motor PTC (Code 12)
Possible causes : Motor ventilation blocked
Motor duty cycle exceeded
PTC open or shorted
Possible solutions : Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling
Check resistance of PTC
Fault name : Open Bypass with phase indication (Code 13, 14 or 15)
Possible causes : Control voltage is low
Inoperable power module bypass
Possible solutions : Check control voltage power supply
Replace power module
Check control module TB2…TB4 and TB5…TB7 for securness
Check Aux 1, 2, 3, 4 configurations are not sent to External Bypass
Fault name : No load fault (Code 16, 17, 18 or 40)
Possible causes : Loss or load side power wiring
Start command cycled unexpectedly with motor rotating
Possible solutions : Check all load side power connections
Check motor windings
Fault name : Line unbalance (Code 19)
Possible causes : Supply unbalance is greater than the user-programmed value
The delay time is too short for the application
Possible solutions : Check power system and correct if necessary
Extend the delay time to match the application requirements
Fault name : Overvoltage (Code 20)
Possible causes : Supply voltage is greater than user programmed value
The delay time is too short for the application
Possible solutions : Check power system and correct if necessary
Correct the user-programmed value
Extend the delay time to match the application requirements.
Fault name : Undervoltage (Code 21)
Possible causes : Supply voltage is less than user programmed value
The delay time is too short for the application
Possible solutions : Check power system and correct if necessary
Correct the user-programmed value
Extend the delay time to match the application requirements.
Fault name : Overload (Code 22)
Possible causes : Motor overloaded
Overload parameters are not matched to the motor
Possible solutions : Check motor overload condition
Check values for overload class and motor FLC
Verify current draw of the motor
Fault name : Undervoltage (Code 23)
Possible causes : Broken motor shaft, belts, toolbits etc…
Pump cavitation
Incorrect user setting
Possible solutions : Check pump system, machine drive components, and loading
Check settings
Repair or replace motor
Fault name : Jam (Code 24)
Possible causes : Motor current has exceeded the user programmed jam level
Possible solutions : Correct source of jam or excessive loading
Check programmed time value
Fault name : Ground fault (Code 33)
Possible causes : Ground fault current level has exceeded programmed value
The delay time is too short for the application
Possible solutions : Check power system and motor; correct if necessary
Check programmed ground fault levels to match application requirements
Extend the delay time to match the application requirements
Fault name : Power loss with phase indication (Code 35, 36 or 37)
Possible causes : Missing supply phase (as indicated)
Internal CR problem
Possible solutions : Check for open line (i.e., blown line fuse)
Replace power pole as indicated
Fault name : Line loss with phase indication (Code 41, 42 or 43)
Possible causes : Incoming 3-phrase voltage instability or distortion
High impedance connection
Possible solutions : Check supply voltage for capability to start/stop motor
Check for loose connections on line side or motor side or power wires
Verify and correct input power quality