Équivalent:
25A-B062N104 PowerFlex 527
Ampérage: 62.1 Ampères
Tension: 240 V (Sans filtre)
Série: PowerFlex 525
INSPECTION GRATUITE POUR CETTE DRIVE
CENTRE DE SERVICE AUTORISÉ YASKAWA AU CANADA
25B-B062N104 Allen Bradley
Numéro de pièce du fabricant :
123-456-789
Manufacturer part number :
25B-B062N104
25B-B062N104 Allen Bradley
20 HP , Serial PowerFlex 525
PowerFlex® 525 AC Drives feature an innovative, modular design to support fast and easy installation and configuration. This next generation of compact drives offers embedded EtherNet/IP™ communications, USB programming, and standard safety features. PowerFlex 525 drives, which offer a power rating of 0.4...22 kW (0.5...30 Hp) with global voltage classes of 100...600V, provide a variety of motor control and flexible mounting options. PowerFlex 525 AC drives operate at temperatures as high as 70 °C (158 °F), and they are ideal for applications such as conveyors, fans, pumps, and mixers.
Error codes
Fault name + Fault # : Power Loss #F003
Description : Single phase operation detected with excessive load.
Action : • Monitor the incoming AC line for low voltage or line power interruption.
• Check input fuses.
• Reduce load.
Fault name + Fault # : UnderVoltage #F004
Description : DC bus voltage fell below the minimum value.
Action : Monitor the incoming AC line for low voltage or line power interruption.
Fault name + Fault # : OverVoltage #F005
Description : DC bus voltage exceeded maximum value.
Action : Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option.
Fault name + Fault # : Motor Stalled #F006
Description : Drive is unable to accelerate or decelerate motor.
Action : • Increase P041, A442, A444, A446 [Accel Time x] or reduce load so driveoutput current does not exceed thecurrent set by parameter A484, A485 [Current Limit x] for too long.
• Check for overhauling load.
Fault name + Fault # : Motor Overload #F007
Description : Internal electronic overload trip.
Action : • An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter Motor OL Current.
• Verify A530 [Boost Select] setting.
Fault name + Fault # : Heatsink OvrTmp #F008
Description : Heatsink/Power Module temperature exceeds a predefined value.
Action : • Check for blocked or dirty heat sink fins. Verify that ambient temperature has not exceeded the rated ambient temperature.
• Check fan.
Fault name + Fault # : Ground Fault #F013
Description : A current path to earth ground has been detected at one or more of the drive output terminals.
Action : Check the motor and external wiring to the drive output terminals for a grounded condition.
Fault name + Fault # : Load Loss #F015
Description : The output torque current is below the value programmed in A490 [Load Loss Level] for a time period greater than the time programmed in A491 [Load Loss Time].
Action : • Verify connections between motor and load.
• Verify level and time requirements
Fault name + Fault # : Output Ph Loss #F021
Description : Output Phase Loss (if enabled). Configure with A557 [Out Phas Loss En].
Action : • Verify motor wiring.
• Verify motor.
Fault name + Fault # : Phase UV Short #F041
Description : Excessive current has been detected between these two output terminals.
Action : • Check the motor and drive output terminal wiring for a shorted condition.
• Replace drive if fault cannot be cleared.
Fault name + Fault # : Phase UV Short #F042
Description : Excessive current has been detected between these two output terminals.
Action : • Check the motor and drive output terminal wiring for a shorted condition.
• Replace drive if fault cannot be cleared.
Fault name + Fault # : Phase UV Short #F043
Description : Excessive current has been detected between these two output terminals.
Action : • Check the motor and drive output terminal wiring for a shorted condition.
• Replace drive if fault cannot be cleared.
Fault name + Fault # : Drive Overload #F064
Description : Drive overload rating has been exceeded.
Action : Reduce load or extend Accel Time.
Fault name + Fault # : Parameter Chksum #F100
Description : Drive parameter non-volatile storage is corrupted.
Action : Set parameter Reset To Defalts to 2 “Factory Rset”.