top of page

CIMR-F7U4011 Yaskawa

Cross references : 3G3RV-A4110 Omron Amperage: 27 Amps Voltage: 480 V Serial: F7 FREE INSPECTION FOR THIS DRIVE CANADA YASKAWA AUTHORIZED SERVICE CENTRE

Numéro de pièce du fabricant : 

123-456-789

Manufacturer part number : 

CIMR-F7U4011

Détails

CIMR-F7U4011 Yaskawa 

 

3G3RV-A4110 Omron


15 HP, Serial F7

The F7 drive was the Industrial Workhorse of adjustable frequency drives. It was intended to handle every conventional drive application found in the typical industrial manufacturing plant from simple variable torque pumping to sophisticated networked material handling. The F7 / Configured package provided an F7 drive in a NEMA Type 12 or NEMA 12 FVFF enclosure, with space for factory-mounted and wired options, such as reactors, filters, circuit breakers, fuses, network communications and I/O cards, etc. 


Error codes

 

 

 

 

BUS

Description : Option Communication Error. After initial communication was established, the connection was lost.

Solution : Check all connections and verify all user-side software configurations.

CPF00

Description1 : Operator Communication Fault. Transmission between the Drive and the Digital Operator was not established within 5 seconds after supplying power.Solution 1 : Remove the Digital Operator, and then reinstall it. 

Description2 : External RAM of CPU was defective.

Solution 2 : Cycle power to the drive.

                     Replace the control board.

 

 

EF0

 

Description : Option Board External Fault.

Solution : Check for an external condition.

                 Verify the parameters.

                 Verify communication signal.

 

EF3

 

Description : External Fault at Terminal S3-S8. Detected when terminals S3-S8 (H1-01 to H1-06) are programmed for external fault function that stops the Drive using ramp to stop, coast to stop, or fast stop.

Solution : Eliminate the cause of the external fault condition. Call us 418-228-5984.

 

EF4

 

Description : External Fault at Terminal S3-S8. Detected when terminals S3-S8 (H1-01 to H1-06) are programmed for external fault function that stops the Drive using ramp to stop, coast to stop, or fast stop.

Solution : Eliminate the cause of the external fault condition. Call us 418-228-5984.

 

EF5

 

Description : External Fault at Terminal S3-S8. Detected when terminals S3-S8 (H1-01 to H1-06) are programmed for external fault function that stops the Drive using ramp to stop, coast to stop, or fast stop.

Solution : Eliminate the cause of the external fault condition. Call us 418-228-5984.

 

EF6

 

Description : External Fault at Terminal S3-S8. Detected when terminals S3-S8 (H1-01 to H1-06) are programmed for external fault function that stops the Drive using ramp to stop, coast to stop, or fast stop.

Solution : Eliminate the cause of the external fault condition. Call us 418-228-5984.

 

EF7

 

Description : External Fault at Terminal S3-S8. Detected when terminals S3-S8 (H1-01 to H1-06) are programmed for external fault function that stops the Drive using ramp to stop, coast to stop, or fast stop.

Solution : Eliminate the cause of the external fault condition. Call us 418-228-5984.

 

 

EF8

 

Description : External Fault at Terminal S3-S8. Detected when terminals S3-S8 (H1-01 to H1-06) are programmed for external fault function that stops the Drive using ramp to stop, coast to stop, or fast stop.

Solution : Eliminate the cause of the external fault condition. Call us 418-228-5984.

 

GF

 

Description : Output Ground Fault. Drive output grounding current has exceeded 50% of the Drive rated output current and L8-09=1.

Solution : Remove the motor and run the Drive without the motor.

                 Check the motor for a phase to ground short.

                 Check the output current with a clamp on meter to verify the DCCT reading.

                 

 

LF

 

Description : Output Open-phase. An open-phase occured at the Drive output. This fault is detected when output current has exceeded 5% imbalance and L8-07=1.

Solution : Check the wiring to the motor. Check the motor for phase to ground short.

                 Check the motor and the Drive Capacity.

                 Add additional impedance.

 

OL1

 

Description : Motor overload. Detected when L1-03 =1 or 3 and the Drive’s output current exceeded the motor overload curve. The overload curve is adjustable using parameter E2-01, L1-01, and L1-02.

Solution : Recheck the cycle time and the size of the load as well as the time set in C1-01 and C1-02.

                 Review the V-F pattern parameters, E1-01 thru E1-13.

                 Check the motor rated current value in E2-01.

 

OL2

 

Description : Drive Overload. The drive output current exceeded the Drive’s overload curve.

Solution : Recheck the cycle time and the size of the load as well as the dimes set in C1-01 and C1-02.

                 Review the V-F pattern parameters, E1-01 thru E1-13.

                 Change to a larger size Drive.

 

OL3

 

Description : Overtorque Detection 1. Drive output current > L6-02 for more than the time set in L6-03 and L6-01 3 or 4.

Solution : Ensure the values is in L6-02 and L6-03 are appropriate.

                 Check application/machine status to eliminate fault.

 

OL4

 

Description : Overtorque Detection 2. Drive output current > L6-05 for more than the time set in L6-06 and L6-04=3 or 4.

Solution : Endure the values is in L6-05 and L6-06 are appropriate.

                 Check application/machine status to eliminate fault.

 

 

 

 

OV 

 

Description : DC bus Overvoltage. The DC bus voltage has exceeded the trip point.

                       208-240 Vac : Trip point is 410 Vdc.

                       480 Vac : Trip point is 820 Vdc.

Solution : Check the input circuit and reduce the input power to within specifications.

                 Extend the time in C1-02 or other active decel settings used such as C1-04, C1-06,C1-08 or C1-09.

                 Remove the power factor correction capacitors.

 

PF

 

Description : Input Phase Loss. Drive input power supply has an open phase or has a large imbalance of voltage. Detected when L8-05=1.

Solution : Check the input voltage.

                 Tighten the terminal screws.

                 

                  

PUF

 

Description : DC Bus Fuse. Detects if the DC bus fuse has opened.

Solution : Remove power from the Drive.

                 Disconnect the motor.

                 Perform the checks without power in Table 6.6.

                 Replace the shorted component(s)

                 Replace the defective fuse.

 

RR

 

Description : Dynamics Braking Transistor. The built-in dynamic braking transistor failed.

Solution : Cycle power to the drive.

                 Replace defective dynamic braking transistor or resistor.

                 Monitor DC bus voltage.

 

UV1 

 

Description : DC bus undervoltage.

                       208-240 Vac : Default trip point is ≤190 Vdc.

                       480 Vac : Default trip point is ≤380 Vdc.

                      Trip point is adjustable in L2-05.

                       Detected then the DC bus voltage is ≤ L2-05.

Solution : Check the input circuit and increase the input power to within specifications.

                 Extend the time in C1-01 or other active accel settings used such as C1-03, C1-05, or C1-07.

                 Check the input voltage.

Équivalents:
3G3RV-A4110 Omron

Ampérage: 27 Ampères
Tension: 480 V
Série: F7

INSPECTION GRATUITE POUR CETTE DRIVE

CENTRE DE SERVICE AUTORISÉ YASKAWA AU CANADA

CIMR-F7U4011 Yaskawa

bottom of page